Refrigerant quality and the AHRI 700 standard

Refrigerants

Many people in the HVACR industry still believe that only new (virgin) refrigerant guarantees the highest quality. In practice, this isn’t always true. Properly reclaimed refrigerant meets the same quality specifications as virgin refrigerant, and in some cases exceeds them. To understand why, it’s worth looking at the AHRI 700 standard, which sets out quality requirements for refrigerants.

What parameters determine refrigerant quality?

The Air-Conditioning, Heating, and Refrigeration Institute (AHRI) is a North American trade association of manufacturers of air-conditioning, heating and commercial refrigeration equipment. One of its activities is carrying out research and setting standards for the refrigeration industry. AHRI developed the AHRI 700 standard, which defines the refrigerant parameters that affect the safety of refrigeration systems and the limits for each. These parameters, together with the possible consequences of exceeding them, are shown in Table 1.

Table 1. Refrigerant quality parameters.
Compiled by PROZON Foundation based on the AHRI 700 standard.

ParameterPermissible limitRisk if exceeded
Impurities≤ 0.5% by weightLower cooling capacity
Non-condensable gases≤ 1.5% by volumeAltered thermodynamic properties
Reduced system efficiency
Risk of chemical reactions
Moisture≤ 10 ppmCorrosion of system components
Ice forming in the capillary tube or expansion valve
Refrigerant decomposition and risk of acid formation
Risk of valve blockage
Acidity≤ 1 ppmCorrosion of system components
Oil degradation
Damage to compressor motor windings
Chlorides0Corrosion of system components
Faster breakdown of refrigerant and oil
Poorer system performance
High-boiling residue≤ 0.01% by volumeClogged filters, valves and capillary tubes
Compressor damage
Particulates0

Does new refrigerant always mean the highest quality?

These requirements show that refrigerant quality is crucial to the safety and correct operation of a system. But it’s just as important to confirm that the refrigerant on offer actually meets AHRI 700. To be sure that it does, you need to buy it from a trusted source. Refrigerants sold at unusually low prices, often illegally imported, still appear on the market. With these, the buyer can’t be sure that the refrigerant’s composition stayed uniform while it was transported in multi-tonne tanks and transferred into smaller containers. If the refrigerant isn’t properly mixed before filling, and the whole process isn’t carried out to the highest quality standards and confirmed by laboratory testing, the buyer has no guarantee that the refrigerant meets AHRI 700. This creates a risk of faulty operation and even damage to the refrigeration system.

The reclamation process – from recovery to quality certification

Reclamation is a technological process that removes contaminants such as oil, moisture, non-condensable gases, acids, chlorides and particulates from recovered refrigerant. Once the process is complete, every batch should undergo laboratory analysis to confirm that it meets AHRI 700. If it doesn’t meet the quality specifications, the refrigerant goes through further cleaning stages or composition adjustment until it does.

At PROZON Climate Protection Foundation, we put refrigerant quality first. Every batch of reclaimed refrigerant goes through full quality control in our in-house laboratory. Once it’s confirmed to meet AHRI 700, it receives an individual batch number and a quality certificate.

How refrigerant is packaged and transported also matters for safety. Refrigerant from illegal sources is often sold in disposable cylinders that don’t meet safety standards.

Key takeaways

Reclamation also makes economic and environmental sense. Restoring recovered refrigerant to usable condition usually costs less than buying a new product. At the same time, reclamation extends the refrigerant’s life cycle, reducing the need for new chemical raw materials and the energy needed to produce virgin refrigerant.

All of these aspects are summarised in Table 2.

Table 2. Virgin refrigerant from unverified sources compared with refrigerant reclaimed by PROZON Foundation.
Compiled by PROZON Foundation.

AspectVirgin refrigerant of unverified originRefrigerant reclaimed by PROZON
Composition testingNo testing after transfer from a multi-tonne tank into smaller cylindersTested at every stage of the process
OriginUnknown, often smuggledLegal
PackagingOften dirty and non-compliantAlways clean and certified in line with UDT (Polish Office of Technical Inspection) requirements
PriceHigher than the cost of reclamationReclamation costs less than buying virgin refrigerant
EnvironmentMore raw materials and energy used in production → larger carbon footprintExtends the refrigerant’s life cycle, reducing the need to produce virgin refrigerant and limiting thermal destruction → smaller carbon footprint
System safetyPoor refrigerant quality leads to equipment failure, higher energy consumption and lower cooling efficiencyParameters compliant with AHRI 700 keep the system safe

From a technical point of view, refrigerant quality isn’t determined by whether it’s virgin or reclaimed, but by laboratory-confirmed compliance with AHRI 700. Choosing refrigerant from a trusted, legal source such as PROZON Climate Protection Foundation reduces the risk of system failure, keeps the system energy-efficient and supports the circular economy.